Risk | Medium |
Patch available | YES |
Number of vulnerabilities | 1 |
CVE-ID | CVE-2019-10995 |
CWE-ID | CWE-798 |
Exploitation vector | Local network |
Public exploit | Public exploit code for vulnerability #1 is available. |
Vulnerable software |
BSP UN30 Server applications / SCADA systems PB610 Panel Builder 600 Server applications / SCADA systems |
Vendor | ABB |
Security Bulletin
This security bulletin contains one medium risk vulnerability.
EUVDB-ID: #VU19017
Risk: Medium
CVSSv4.0: 7.4 [CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:P/U:Green]
CVE-ID: CVE-2019-10995
CWE-ID:
CWE-798 - Use of Hard-coded Credentials
Exploit availability: No
DescriptionThe vulnerability allows an attacker to gain full access to vulnerable system.
The vulnerability exists due to the CP651 HMI component implements hidden administrative accounts that are used during the provisioning phase of the HMI interface. An unauthenticated attacker can prevent legitimate access to an affected system node, take control of it, or insert and run arbitrary code in an affected system.
Successful exploitation of this vulnerability may result in complete compromise of vulnerable system.
MitigationInstall updates from vendor's website.
Vulnerable software versionsBSP UN30: All versions
PB610 Panel Builder 600: 1.91 - 2.8.0.367
CPE2.3https://ics-cert.us-cert.gov/advisories/icsa-19-178-02
https://library.e.abb.com/public/b2edb894b46242fda29eb7644a068161/ABB-Advisory_3ADR010402.pdf
Q & A
Can this vulnerability be exploited remotely?
Yes. This vulnerability can be exploited by a remote non-authenticated attacker via the local network (LAN).
How the attacker can exploit this vulnerability?
The attacker would have to send a specially crafted request to the affected application in order to exploit this vulnerability.
Is there known malware, which exploits this vulnerability?
No. We are not aware of malware exploiting this vulnerability. However, proof of concept for this vulnerability is available.