Denial of service in Siemens SIPROTEC 4 and SIPROTEC Compact



Risk Medium
Patch available NO
Number of vulnerabilities 1
CVE-ID CVE-2019-19279
CWE-ID CWE-20
Exploitation vector Network
Public exploit N/A
Vulnerable software
SIPROTEC 4
Hardware solutions / Security hardware applicances

Siprotec Compact
Hardware solutions / Security hardware applicances

Vendor Siemens

Security Bulletin

This security bulletin contains one medium risk vulnerability.

1) Input validation error

EUVDB-ID: #VU25267

Risk: Medium

CVSSv4.0: 6.6 [CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:U/U:Green]

CVE-ID: CVE-2019-19279

CWE-ID: CWE-20 - Improper input validation

Exploit availability: No

Description

The vulnerability allows a remote attacker to perform a denial of service (DoS) attack.

The vulnerability exists due to insufficient validation of user-supplied input in the EN100 Ethernet communication modules. A remote attacker can send a specially crafted packets to Port 50000/UDP and cause a denial of service condition on the target system.

Mitigation

Cybersecurity Help is currently unaware of any official solution to address this vulnerability.

Vulnerable software versions

SIPROTEC 4: All versions

Siprotec Compact: All versions

CPE2.3 External links

https://ics-cert.us-cert.gov/advisories/icsa-20-042-12
https://cert-portal.siemens.com/productcert/pdf/ssa-974843.pdf


Q & A

Can this vulnerability be exploited remotely?

Yes. This vulnerability can be exploited by a remote non-authenticated attacker via the Internet.

Is there known malware, which exploits this vulnerability?

No. We are not aware of malware exploiting this vulnerability.