Risk | High |
Patch available | YES |
Number of vulnerabilities | 1 |
CVE-ID | CVE-2020-12029 |
CWE-ID | CWE-20 |
Exploitation vector | Network |
Public exploit | Public exploit code for vulnerability #1 is available. |
Vulnerable software Subscribe |
FactoryTalk View SE Server applications / SCADA systems |
Vendor | Rockwell Automation |
Security Bulletin
This security bulletin contains one high risk vulnerability.
EUVDB-ID: #VU29157
Risk: High
CVSSv3.1: 9.1 [CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:F/RL:O/RC:C]
CVE-ID: CVE-2020-12029
CWE-ID:
CWE-20 - Improper input validation
Exploit availability: Yes
DescriptionThe vulnerability allows a remote attacker to execute arbitrary code on the system.
The vulnerability exists due to insufficient validation of user-supplied input in filenames within a project directory. A remote attacker can use a specially crafted file and execute arbitrary code on the target system.
MitigationVendor recommends applying patch 1126289. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx.
Vulnerable software versionsFactoryTalk View SE: All versions
External linkshttp://ics-cert.us-cert.gov/advisories/icsa-20-170-05
Q & A
Can this vulnerability be exploited remotely?
Yes. This vulnerability can be exploited by a remote non-authenticated attacker via the Internet.
How the attacker can exploit this vulnerability?
The attacker would have to send a specially crafted request to the affected application in order to exploit this vulnerability.
Is there known malware, which exploits this vulnerability?
No. We are not aware of malware exploiting this vulnerability. However, a fully functional exploit for this vulnerability is available.