Authentication bypass in SICLOCK TC400 and SICLOCK TC100 - CVE-2018-4852

 

Authentication bypass in SICLOCK TC400 and SICLOCK TC100 - CVE-2018-4852

Published: July 5, 2018


Vulnerability identifier: #VU13568
CSH Severity: Low
CVSS v4.0: CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N/E:P/U:Clear
CVE-ID: CVE-2018-4852
CWE-ID: CWE-592
Exploitation vector: Remote access
Exploit availability: No public exploit available
Vendor: Siemens
Affected software:
SICLOCK TC400
SICLOCK TC100

Detailed vulnerability description

The vulnerability allows a remote attacker to bypass authentication on the target system.
The weakness exists due to unspecified flaw. A remote attacker who is able to obtain certain knowledge specific to the attacked device, can circumvent the authentication mechanism to read and modify the device configuration.


How to mitigate CVE-2018-4852

Siemens has identified the following specific workarounds and mitigations that customers can apply to
reduce the risk:
• Provide redundant time sources and implement plausibility checks for the time information in critical
plant controllers.
• Protect network access to the affected devices with appropriate measures, e.g. protect SICLOCK
TC devices with firewalls to reduce the risk.
It is recommended to filter traffic to all ports excluding those needed for time synchronization. If
time synchronization is performed using NTP, then port 123/udp must be opened on the firewall. If
time synchronization is performed using SIMATIC time synchronization, then port 22223/udp and
port 22224/udp must be opened on the firewall.
For configuring parameters, it is recommended to use a direct connection to the SICLOCK TC.
• Apply the cell protection concept,  and apply defense-in-depth:  https://www.siemens.com/cert/
operational-guidelines-industrial-security

Sources