Resource exhaustion in Siemens products - CVE-2019-10936

 

Resource exhaustion in Siemens products - CVE-2019-10936

Published: October 18, 2019


Vulnerability identifier: #VU21936
CSH Severity: Medium
CVSS v4: 8.7 [CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N]
CVE-ID: CVE-2019-10936
CWE-ID: CWE-400
Exploitation vector: Remote access
Exploit availability: No public exploit available

Vulnerability details

The vulnerability allows a remote attacker to perform a denial of service (DoS) attack.

The vulnerability exists due to improper resource management when processing UDP packets. A remote attacker can send a large amount of specially crafted UDP packets, trigger resource exhaustion and perform a denial of service (DoS) attack.


Affected software

IM 155-6 PN HS
SINAMICS DCP
SIMATIC ET 200AL
SIMATIC ET 200M
IM 155-5 PN BA
IM 155-5 PN HF
IM 155-5 PN ST
SIMATIC ET 200S
IM 155-6 PN BA
IM 155-6 PN HA
IM 155-6 PN HF
IM 155-6 PN ST
IM 155-6 PN/2 HF
SIMATIC PN/PN Coupler
SIMATIC ET 200pro
SIMATIC ET 200ecoPN
IM 155-6 PN/3 HF
SINAMICS G120
SINAMICS SM120
SINAMICS SL150
SINAMICS S150
SINAMICS S120
SINAMICS S110
SINAMICS GM150
SINAMICS GL150
SINAMICS GH150
SINAMICS G150
SINAMICS G130
SINAMICS G110M
SINAMICS DCM
SIMATIC WinAC RTX (F) 2010
SIMATIC S7-400H V6
SIMATIC S7-410 V8
SIMATIC S7-400 V6
SIMATIC S7-300
SIMATIC S7-1500 CPU
SIMATIC CFU PA
SIMATIC S7-1200
SINUMERIK 840D sl
SIMATIC HMI KTP Mobile Panels
SIMATIC HMI Comfort Panels 4”-22”
SIMATIC HMI Comfort Outdoor Panels 7” & 15”
SINUMERIK 828D
SIMATIC S7-400 PN/DP V7
SIMATIC PROFINET Driver

How to mitigate CVE-2019-10936

Install updates from vendor's website for the following products:
  • Development/Evaluation Kits for PROFINET IO:
    • DK Standard Ethernet Controller: All versions
    • EK-ERTEC 200: All versions
    • EK-ERTEC 200P: All versions
  • SIMATIC CFU PA: All versions prior to 1.2.0
  • SIMATIC ET 200AL: All versions
  • SIMATIC ET 200M: All versions
  • SIMATIC ET 200MP IM 155-5 PN BA: All versions prior to 4.2.3
  • SIMATIC ET 200MP IM 155-5 PN HF: All versions
  • SIMATIC ET 200MP IM 155-5 PN ST: All versions
  • SIMATIC ET 200S: All versions
  • SIMATIC ET 200SP IM 155-6 PN BA: All versions
  • SIMATIC ET 200SP IM 155-6 PN HA: All versions
  • SIMATIC ET 200SP IM 155-6 PN HF: All versions prior to 4.2.2
  • SIMATIC ET 200SP IM 155-6 PN HS: All versions
  • SIMATIC ET 200SP IM 155-6 PN ST: All versions
  • SIMATIC ET 200SP IM 155-6 PN/2 HF: All versions prior to 4.2.2
  • SIMATIC ET 200SP IM 155-6 PN/3 HF: All versions prior to 4.2.1
  • SIMATIC ET 200ecoPN (except 6ES7148-6JD00-0AB0 and 6ES7146-6FF00-0AB0): All versions
  • SIMATIC ET 200pro: All versions
  • SIMATIC HMI Comfort Outdoor Panels 7" & 15": All versions
  • SIMATIC HMI Comfort Panels 4" - 22": All versions
  • SIMATIC HMI KTP Mobile Panels: All versions
  • SIMATIC PN/PN Coupler: All versions
  • SIMATIC PROFINET Driver: All versions prior to 2.1
  • SIMATIC S7-1200 CPU family (incl. F): All versions
  • SIMATIC S7-1500 CPU family (incl. F): All versions prior to 2.0
  • SIMATIC S7-300 CPU family (incl. F): All versions
  • SIMATIC S7-400 PN/DP V7 (incl. F): All versions
  • SIMATIC S7-400 V6 (incl. F) and below: All versions
  • SIMATIC S7-400H V6: All versions prior to 6.0.9
  • SIMATIC S7-410 V8: All versions
  • SIMATIC WinAC RTX (F) 2010: All versions prior to SP3
  • SINAMICS DCM: All versions prior to 1.5 HF1
  • SINAMICS DCP: All versions
  • SINAMICS G110M v4.7 (PN Control Unit): All versions prior to 4.7 SP10 HF5
  • SINAMICS G120 v4.7 (PN Control Unit): All versions prior to 4.7 SP10 HF5
  • SINAMICS G130 v4.7 (Control Unit and CBE20): All versions
  • SINAMICS G150 (Control Unit and CBE20): All versions
  • SINAMICS GH150 v4.7 (Control Unit): All versions
  • SINAMICS GL150 v4.7 (Control Unit): All versions
  • SINAMICS GM150 v4.7 (Control Unit): All versions
  • SINAMICS S110 (Control Unit): All versions
  • SINAMICS S120 v4.7 (Control Unit and CBE20): All versions
  • SINAMICS S150 (Control Unit and CBE20): All versions
  • SINAMICS SL150 v4.7 (Control Unit): All versions
  • SINAMICS SM120 v4.7 (Control Unit): All versions
  • SINUMERIK 828D: All versions prior to 4.8 SP5
  • SINUMERIK 840D sl: All versions

IM 155-5 PN BA - update to 4.2.3
IM 155-6 PN HF - update to 4.2.2
IM 155-6 PN/2 HF - update to 4.2.2
SIMATIC PROFINET Driver - update to 2.1
IM 155-6 PN/3 HF - update to 4.2.1
SINAMICS G120 - update to 4.7 SP10 HF5
SINUMERIK 828D - update to 4.8 SP5
SINAMICS G110M - update to 4.7 SP10 HF5
SINAMICS DCM - update to 1.5 HF1
SIMATIC WinAC RTX (F) 2010 - update to SP3
SIMATIC S7-400H V6 - update to 6.0.9
SIMATIC S7-1500 CPU - update to 2.0
SIMATIC CFU PA - update to 1.2.0

External References

Related Security Bulletins