Vulnerability identifier: #VU17655
Vulnerability risk: Low
CVSSv3.1: 6.5 [CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:U/RL:O/RC:C]
CVE-ID:
CWE-ID:
CWE-20
Exploitation vector: Network
Exploit availability: No
Vulnerable software:
SIMATIC S7-300
Hardware solutions /
Firmware
Vendor: Siemens
Description
The vulnerability allows a remote attacker to perform a denial of service (DoS) attack.
The vulnerability exists due to insufficient validation of user-supplied input. A remote attacker can send a specially crafted S7 communication packet to a communication interface of the CPU and cause a denial-of-service condition of the core functionality of the CPU.
Mitigation
Update to version 3.X.16.
Vulnerable software versions
SIMATIC S7-300: 2.0.0 - 3.3.0
External links
http://cert-portal.siemens.com/productcert/pdf/ssa-306710.pdf
Can this vulnerability be exploited remotely?
Yes. This vulnerability can be exploited by a remote non-authenticated attacker via the Internet.
Is there known malware, which exploits this vulnerability?
No. We are not aware of malware exploiting this vulnerability.