Vulnerability identifier: #VU7384
Vulnerability risk: Medium
CVSSv3.1: 8.5 [CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:U/RL:O/RC:C]
CVE-ID:
CWE-ID:
CWE-20
Exploitation vector: Network
Exploit availability: No
Vulnerable software:
SIPROTEC 4
Hardware solutions /
Security hardware applicances
Siprotec Compact
Hardware solutions /
Security hardware applicances
Vendor: Siemens
Description
The vulnerability allows a remote attacker to bypass security restrictions.
The weakness exists due to an error related to EN100 Ethernet module. A remote attacker can send specially crafted HTTP request and bypass access restrictions.
Successful exploitation of the vulnerability results in administrative access to the system.
Mitigation
Update SIPROTEC 4 to version 4.29.
Update SIPROTEC Compact to version 4.29.
Vulnerable software versions
SIPROTEC 4: 4.24 - 4.28
Siprotec Compact: 4.24 - 4.28
External links
http://www.siemens.com/cert/pool/cert/siemens_security_advisory_ssa-630413.pdf
Can this vulnerability be exploited remotely?
Yes. This vulnerability can be exploited by a remote non-authenticated attacker via the Internet.
Is there known malware, which exploits this vulnerability?