SB2020111109 - Multiple vulnerabilities in Schneider Electric PLC Simulator for EcoStruxure Control Expert



SB2020111109 - Multiple vulnerabilities in Schneider Electric PLC Simulator for EcoStruxure Control Expert

Published: November 11, 2020 Updated: December 14, 2020

Security Bulletin ID SB2020111109
CSH Severity
High
Patch available
YES
Number of vulnerabilities 5
Exploitation vector Remote access
Highest impact Code execution

Breakdown by Severity

High 40% Medium 40% Low 20%
  • Low
  • Medium
  • High
  • Critical

Description

This security bulletin contains information about 5 vulnerabilities.


1) Improper Check for Unusual or Exceptional Conditions (CVE-ID: CVE-2020-7538)

CWE-ID: CWE-754 - Improper Check for Unusual or Exceptional Conditions

CVSSv4: CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:U/U:Green


The vulnerability allows a remote attacker to perform a denial of service (DoS) attack.

The vulnerability exists due to improper input validation. A remote attacker can send a specially crafted request over Modbus and cause denial of service condition.


2) Download of code without integrity check (CVE-ID: CVE-2020-28213)

CWE-ID: CWE-494 - Download of Code Without Integrity Check

CVSSv4: CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:H/VA:H/SC:N/SI:N/SA:N/E:U/U:Green


The vulnerability allows a remote attacker to compromise the affected system

The vulnerability exists due to software does not perform software integrity check when downloading updates. A remote authenticated attacker can send specially crafted requests over Modbus and execute arbitrary commands on the target system. 


3) Improper Restriction of Excessive Authentication Attempts (CVE-ID: CVE-2020-28212)

CWE-ID: CWE-307 - Improper Restriction of Excessive Authentication Attempts

CVSSv4: CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:U/U:Amber


The vulnerability allows a remote attacker to gain access to the system.

The vulnerability exists due to the authentication mechanism has no brute-force prevention. A remote attacker can launch a brute-force authentication attack and cause unauthorized command execution.


4) Improper Authorization (CVE-ID: CVE-2020-28211)

CWE-ID: CWE-285 - Improper Authorization

CVSSv4: CVSS:4.0/AV:L/AC:L/AT:N/PR:H/UI:A/VC:N/VI:N/VA:N/SC:H/SI:H/SA:N/E:U/U:Clear


The vulnerability allows a local user to bypass authorization checks.

The vulnerability exists due to improper authorization check. A local administrator can bypass authentication when overwriting memory using a debugger.


5) Stack-based buffer overflow (CVE-ID: CVE-2020-7559)

CWE-ID: CWE-121 - Stack-based buffer overflow

CVSSv4: CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:U/U:Amber


The vulnerability allows a remote attacker to execute arbitrary code on the target system.

The vulnerability exists due to a boundary error in the Modbus message-processing functionality. A remote unauthenticated attacker can send a specially crafted request, trigger stack-based buffer overflow and execute arbitrary code on the target system.

Successful exploitation of this vulnerability may result in complete compromise of vulnerable system.


Remediation

Install update from vendor's website.