#VU21508 Buffer overflow in Schneider Electric products - CVE-2018-7851


Vulnerability identifier: #VU21508

Vulnerability risk: Medium

CVSSv4.0: 2.3 [CVSS:4.0/AV:N/AC:L/AT:P/PR:L/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:U/U:Green]

CVE-ID: CVE-2018-7851

CWE-ID: CWE-119

Exploitation vector: Network

Exploit availability: No

Vulnerable software:
BMxCRA312xx
Hardware solutions / Firmware
140CRA312xxx
Hardware solutions / Firmware
Modicon Premium
Hardware solutions / Firmware
Modicon M340
Hardware solutions / Firmware
Modicon M580
Hardware solutions / Firmware

Vendor: Schneider Electric

Description

The vulnerability allows a remote attacker to cause a denial of service (DoS) condition on the target system.

The vulnerability exists due to a boundary error when sending a specially crafted Modbus packet. A remote authenticated attacker can trigger memory corruption and cause a denial of service condition to the device that would force a restart to restore availability.


Mitigation

Install updates from vendor's website.
Note: BMXCRA31210C, BMXCRA31210 and BMXCRA31200 update to firmware V2.40.

Vulnerable software versions

BMxCRA312xx: before 2.40

140CRA312xxx: All versions

Modicon Premium: All versions

Modicon M340: before 3.01

Modicon M580: 1.04 - 2.41


External links
https://www.schneider-electric.com/en/download/document/SEVD-2019-134-10/